← Back to guides
GuideModification guide

How should an HVAC modification be reviewed?

A practical framework for checking normal ventilation, fire mode, microbial control, maintenance access, controls and recommissioning before changing HVAC plant.

A fan or AHU replacement can look simple until the same equipment is found to carry outdoor air, pressure relationships, fire-mode functions, drainage and maintenance responsibilities.

01

The practical answer

Define every function the affected equipment performs before selecting the replacement. Review normal mode, fire mode, controls, power, moisture and maintainability as separate but connected design cases, then recommission the complete changed system.

The best modification scopes prevent hidden interfaces from emerging during commissioning. That means recovering the current ventilation basis, fire matrix, control sequence and maintenance condition before the new equipment is locked in.

AS 1668.2, AS 1668.1 and AS/NZS 3666.1 can all apply to one AHU for different reasons. The project should show which requirements are being checked rather than saying simply ‘designed to AS 1668’.

The final verification should test the changed system in the modes that matter. Individual factory data and component checks do not prove the installed building system performs correctly.

02

When this guide is useful

Use this guide when
  • Replacing an AHU, supply fan or exhaust fan.
  • Changing VAV boxes, dampers or controls.
  • Reconfiguring ductwork during a tenancy fit-out.
  • Adding kitchen or process exhaust.
  • Upgrading plant where access, drainage or hygiene problems already exist.
Do not use it to
  • Routine filter replacement or minor maintenance with no change to the engineering basis.
  • Assuming the current documentation is correct without field verification.
  • Treating the controls contractor as the sole owner of fire-mode logic.
  • Avoiding recommissioning because the replacement equipment has a factory test certificate.
03

A seven-part HVAC modification review

Each part asks what function could change. The scope should close the loop from design basis to field commissioning.

01

Define the modification boundary

Identify equipment, ducts, dampers, controls, power, drains and spaces affected directly or indirectly.

02

Confirm current building use

Check whether occupancy and room functions still match the original ventilation design.

03

Review normal ventilation

Outdoor air, supply, exhaust, make-up air, pressure and operating schedules under AS 1668.2 as relevant.

04

Review natural and mixed-mode assumptions

Check AS 1668.4 where the design relies on permanent openings or interaction with natural ventilation.

05

Review fire mode

Use the fire matrix and AS 1668.1 to identify shutdown, pressurization, smoke exhaust, damper and override functions.

06

Review hygiene and maintenance

Use AS/NZS 3666.1 to address drainage, wet components, access, intake location and cleanability.

07

Commission and update records

Test the changed normal and fire modes, update drawings, manuals, asset data and maintenance tasks.

04

Detailed engineering examples

These cases show how the framework changes a real engineering decision. They are deliberately written around uncertainty, options and evidence rather than one universal answer.

Case study 1 · AHU replacement

Old AHU replaced with a compact high-efficiency unit

01
The decisionWhat needs to be checked beyond fan duty and coil capacity?
Project context

A new AHU is smaller, more efficient and can meet the normal supply duty. The project team wants to reuse the existing ducts and controls.

What makes the decision difficult

  • The old unit supplies outdoor air to several changed occupancies.
  • It participates in fire-mode operation.
  • The new compact arrangement reduces access around filters and drains.

How the guide should be applied

  1. Confirm current ventilation demand and outdoor-air strategy.
  2. Recover the fire-mode sequence and compare control/power interfaces.
  3. Check condensate drainage, filter access and coil cleaning space.
  4. Define normal-mode and fire-mode commissioning tests before procurement.
Practical outcome

The replacement becomes a coordinated building-services modification with a clear acceptance plan, avoiding late discovery of fire-mode or maintenance problems.

Case study 2 · Kitchen exhaust upgrade

Larger exhaust fan creates building pressure problems

02
The decisionWhy did a successful fan upgrade make the building perform worse?
Project context

A food tenancy increases exhaust duty without coordinated supply or make-up air changes.

What makes the decision difficult

  • Door forces increase.
  • Odours migrate into dining areas.
  • Shared mall air systems are affected.

How the guide should be applied

  1. Review exhaust and replenishment air together.
  2. Map pressure relationships across the tenancy boundary.
  3. Check controls and interlocking.
  4. Commission the final airflow and pressure system.
Practical outcome

The remedy addresses make-up air and controls rather than simply changing the fan again.

Case study 3 · Tenancy fit-out

Duct and VAV changes affect fire-mode operation

03
The decisionCan the fit-out proceed without reviewing smoke control?
Project context

A floor is subdivided and VAV boxes are relocated. The fit-out is treated as a comfort-only mechanical project.

What makes the decision difficult

  • The floor forms part of a zone pressurization system.
  • Damper functions are unclear.
  • The fire matrix is not updated.

How the guide should be applied

  1. Map the fit-out against smoke-control zones.
  2. Define VAV and damper fire-mode positions.
  3. Coordinate the fire matrix.
  4. Test the final sequence after completion.
Practical outcome

The project includes smoke-control coordination and commissioning before occupancy, preventing a hidden fire-mode defect.

05

Common traps

Like-for-like by equipment size

The same airflow or footprint does not prove equivalent controls, fire mode or maintainability.

Reviewing only the new equipment

Existing ducts, dampers, power and controls can govern whether the modification works.

No current-use check

The old plant may already be serving a building that has drifted away from the original occupancy basis.

Commissioning added at the end

Acceptance tests should be defined during design so sensors, access and controls support them.

Ignoring maintenance problems during capital work

A replacement is the best time to correct poor drainage and inaccessible components.

06

Evidence to gather before deciding

Current building use and occupancy

Mechanical drawings and schedules

Fire matrix and smoke-control drawings

BMS and control sequences

Fan, AHU and damper data

Power and wiring interfaces

Drainage and condensate arrangement

Maintenance access requirements

Commissioning history

Proposed equipment and control changes

07

Useful engineering outputs

1

Modification basis

Normal ventilation, natural/mixed-mode, fire-mode and hygiene functions clearly separated.

2

Coordinated design package

Equipment, controls, power, dampers, access and drainage changes with discipline interfaces identified.

3

Commissioning and handover package

Tests, results, updated drawings, manuals, asset data and maintenance tasks for the final system.